Chlorinator with Redox Controller and Pump

Chlorinator depending on the measured Redox value for private or public drinking water. Complete system on panel with instrument for redox, analogue dosing pump, sensor, probe holder and flow sensor.

Flow rate up to 54 l/h.
Pressure max 20 bar.

Typical Installation

 

Chlorinator with Redox Controller and Pump is a compact system for measuring and adjusting the chlorine in private or public water units and water treatment systems. Pump and instrument together in one case (2 in 1). Ideal to treat water systems where the water quality is variable.

 

Pre-installed system on panel or cabinet ready to use. The unit include electromagnetic dosing pump, Rx electrode, probe holder and flow sensor for reliable and safe operation.

 

Set the value of Redox depending on the concentration of residual chlorine. The concentration of free chlorine in the tank being such as to provide a free chlorine in the water supply net at least 0,2 mg/l (ppm).

 

Key Point

For proper chlorination of water is importand a reliable measurement of the Redox value:

 

  • Good mixing of chlorine to water.
  • Proper contact time chlorine-water.
  • Correct point for water sampling.
  • Good maintenance of the electrode (clean).
  • Regular calibration of the electrode.

 

 

Technicals Data

 

MT serie AM serie HY.MT HY.MA
economical
Flow rates 0 ÷ 54 lt/h 0 ÷ 54 lt/h 0 ÷ 5 lt/h 0 ÷ 5 lt/h
Pressure  (max) 20 bar 20 bar 8 bar 8 bar
Manual flow rate requlation 0÷100% 0÷100% 0÷100% 0÷100%
Proportional dosing by signals 0/4÷20mA Χ Χ Χ Χ
Control Chlorination by measured Redox Χ Χ Χ Χ
Control Chlorination by measured free Cl2
Pump LCD back-light display Χ Χ
Pump head PVDF PVDF PVC PVC
Diaphragm PTFE PTFE PTFE PTFE
Ball valves ceramic ceramic ceramic ceramic
Seats FPM or EPDM FPM or EPDM FPM FPM
 Over Feed Alarm (OFA) Χ Χ Χ Χ
Remote controle On/Off Χ Χ
Pump Alarm relay Χ Χ
Instrument Alarm relay Χ Χ Χ Χ
Level control probe Χ Χ Χ Χ
Flow sensor input Χ Χ Χ
Operation status Power-ON (LED) Χ Χ Χ Χ
Level Alarm (LED) Χ Χ Χ Χ
Automatic calibration Χ Χ
Security Password Χ Χ Χ Χ
Statistics pump Χ Χ
Integrated manual vent valve Χ Χ Χ Χ
Standard power supply 100÷240Vac 100÷240Vac 100÷240Vac 100÷240Vac
Installation Kit std PVC std PVC std PP std PP
Information for pump

 

 

Package Included

 

Standard PVC kit

  • Foot filter PVC.
  • Injection valve PVC.
  • 2 m PE delivery tube.
  • 2 m PVC suction tube.
  • Panel
  • Buffer solution 475 mV

Standard PP

  • Foot filter PP.
  • Injection valve PP.
  • 2 m PE delivery tube.
  • 2 m PVC suction tube.
  • Panel
  • Buffer solution 475 mV

PVDF kit (option)

  • Foot filter PVDF.
  • Injection valve PDF.
  • 2 m PE delivery tube.
  • 2 m PVC suction tube.
  • Panel
  • Buffer solution 475 mV

 

Ask A Quote